33InRow RD Operation and Maintenance
Persistant High Discharge
Pressure Fault
Critical • Indicates there were three High Discharge Pressure shutdowns in 30
minutes. Alarms must be cleared manually.
• If the problem persists, contact APC at a number listed on the back
cover of this manual.
High Suction Pressure Fault Warning • Check the air filter and evaporator for obstructions.
• If the problem persists, contact APC at a number listed on the back
cover of this manual.
Internal Communication
Fault
Critical • A hardware failure exists. For assistance, contact APC at a number
listed on the back cover of this manual.
Low Suction Pressure Fault Critical • For assistance, contact APC at a number listed on the back cover of
this manual.
On Standby: Input Contact
Fault
Warning • At the display interface, make sure the Input Normal State is defined
correctly in the Set Unit Threshlds screen.
• Clear the problem that caused the input contact switch to change from
its normal state.
• If the problem persists, contact APC at a number listed on the back
cover of this manual.
Rack Inlet #n High
Temperature Violation
Critical • Make sure the temperature sensor is connected and placed properly.
• Make sure the Rack Inlet threshold is set correctly in the Set Unit
Threshlds screen.
• If the problem persists, contact APC at a number listed on the back
cover of this manual.
Rack Inlet #n Temperature
Sensor Fault
Critical • Make sure the sensors are connected properly.
• If the problem persists, replace the sensor, or contact APC at a number
listed on the back cover of this manual.
Return Air High Temperature
Violation
Warning • Make sure the Return Air threshold is set correctly in the Set Unit
Threshlds screen.
• If the problem persists, contact APC at a number listed on the back
cover of this manual.
Return Air Sensor Fault Critical • Make sure the sensor is connected properly.
• If the problem persists, replace the sensor, or contact APC at a number
listed on the back cover of this manual.
Suction Pressure Sensor
Failure
Warning • A hardware failure exists. For assistance, contact APC at a number
listed on the back cover of this manual.
Supply Air High
Temperature Violation
Warning • Make sure the temperature sensor is connected properly.
• Make sure the Supply Air threshold is set correctly in the Set Unit
Threshlds screen.
• If the problem persists, contact APC at a number listed on the back
cover of this manual.
Supply Air Sensor Fault
(upper or lower)
Critical • Make sure the faulty sensor is connected properly.
• If the problem persists, replace the sensor, or contact APC at a number
listed on the back cover of this manual.
Supply Humidity Sensor
Fault
Critical • Make sure the faulty sensor is connected properly.
• If the problem persists, replace the sensor, or contact APC at a number
listed on the back cover of this manual.
Water Detection Fault Warning • Identify the source of the leak.
• For assistance, contact APC at a number listed on the back cover of
this manual.
Alarm Message Severity Action Required