5.6.4 Operation customizing
You may configure many UPS operations for specific applications. To use
the customizing features of the UPS, you must set all option switches to the
on ( I ) position. The functions ordinarily controlled by the switches are
duplicated in the UPS monitoring software. Once any of the option
switches are returned to the off ( O ) position, functionality of the option
switches is restored.
Battery test operation
You can set the battery test to automatically run at startup, at startup and
once every 7 days, at startup and once every 14 days, or never. The default
setting is at startup and every 14 days.
Transfer voltage
You can configure the UPS’s upper and lower transfer voltages over a wide
range (see Sec. 9.2.)
On-battery output voltage (220/230/240 Vac version only)
You may set the UPS’s on-battery output voltage to a nominal 220, 225, 230
or 240 Vac. The default setting is 225 Vac.
Utility failure sensitivity
You may configure the UPS’s sensitivity to line-voltage distortions to allow
use of the UPS in different electrical environments. You may choose high,
medium, or low sensitivity settings. The high setting provides the best
protection from all utility voltage distortions. The medium setting is
intended for use where rapid low-amplitude line voltage fluctuations occur
frequently as the result of motor load switching in air conditioners, eleva-
tors, etc. The low setting is intended for use when the UPS is operated from
an inexpensive fuel powered generator. The default setting is high.
Low battery warning interval
The UPS’s low battery warning may be set to activate 2, 5, 7 or 10 minutes
before shutdown. The default is 2 minutes.