9.4 Battery and charger UPS version (Vac): 100 120 220/230/240
Battery type: Spill proof, maintenance free sealed lead-calcium.
Typical battery life: 3 to 6 years.
Battery life dependent on number of discharges and ambient temperature.
Low battery signaling: Continuous visual and audible alarm 2 minutes
before shutdown.
Recharge time: 4 to 10 hours typical from total discharge. UPS may be
used immediately after discharge but will provide shorter backup time.
9.5 Surge and noise suppression
Surge energy rating (Joules, maximum): 160 320 320
One occurrence, 10/1000 µs waveform.
Surge current capability (maximum): 6500 Amp peak.
One occurrence, 8/20 µs waveform.
Surge response time: 0 ns (instantaneous) normal mode; less than 5 ns
common mode.
Surge voltage let-through: <0.7% <0.7% <2.0%
per ANSI C62.41 Cat. A 6 kV test.
Noise filter range: 100 kHz to 10 MHz
Normal and common mode EMI/RFI suppression.
9.6 Operating Environment
Temperature: 0 to +40°C (+32 to +104°F)
Relative humidity: 0 to 95%, non-condensing
Operating & storage relative humidity: 0 to 95%, non-condensing
Operating elevation: 0 to 3,000 m (0 to 10,000 ft)
Storage elevation: 0 to 15,000 m (0 to 50,000 ft)
Electromagnetic immunity:
IEC 801-2 level IV, 801-3 level III, 801-4 level IV, 801-5 level III.
Audible noise: <45 dBA at 1 m (3 ft)