APC DCM00K04W481 Datasheet Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 30
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
User Manual 990-9189A
DC MX06 60A Shelf Page 15 of 30 18
th
FEB 02
2.4.3 Temperature Compensation
Temperature compensation / Fixed output voltage selection (SK1)
For “Fixed Output Voltage” SK1-1 to SK1-2 will be linked. (default setting)
For “Temp Comp” remove above mentioned link and fit supplied thermistor kit to SK1.
Temperature compensation uses the thermistor to monitor battery temperature and automatically
adjusts the output voltage of the system. This ensures the charging voltage stays within the battery
manufacturers recommended limits.
DC MX06 60A Calculated Temperature Compensation (54V)
52.00
53.00
54.00
55.00
56.00
57.00
58.00
59.00
-10.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00 70.00
Temperature (°C)
Voltage (V)
Output Voltage max
Output Voltage nom
Output Voltage min
Minimum Battery Voltage
Maximum Battery Voltage
Pin 3
SK1 Pin 2
Pin 1
If temperature compensation is
enabled the output will be as follows:
Nominal Output: 54.5Vdc @ 25°C
Temp coefficient: -76mV/°C ±10%
Page view 14