17MGE™ Galaxy™ 300 10-40 kVA 3:3, 10-30 kVA 3:1 - 380/400/415 V Installation
Battery cabling YUASA 15 kVA 60 min.
No. Item Description Part no. Qty.
A Battery Yuasa battery SWL 1100 912-0001 30
B Copper bar 70*25*2 880-2755 20
C Power cable Wire 16 mm
2
Ivory 380 mm 0W5032 3
D Power cable Wire 16 mm
2
Ivory 640mm 0W5035 3
E Power cable Wire Assy 16 mm
2
Ivory 1200 mm 0W5034 2
F Power cable Wire Assy 16 mm
2
red 900 mm CB+ 0W4982 1
G Power cable Wire Assy 1 string CBN 0W4989 1
H Power cable Wire Assy 16 mm
2
White 900 mm CB- 0W4986 1
*Torque for screws to link
batteries is 2.5 Nm