APC Smart-UPS 750 Specifications Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
8
For more information about all APC products, go to www.apc.com
Smart-UPS
®
XL Series
Achieving 99.999% uptime requires a
UPS with a runtime of greater than one
hour, or a generator.
• Up time levels can be dramatically
enhanced by increasing the run time of
your UPS from five minutes to one hour.
Smart-UPS Availability
1
Transfer points are user-adjustable using included software.
2
Servers and other IT equipment are moving to Power Factor Corrected (PFC) power supplies of 1.0, where the power drawn in Volt-Amps (VA) is equal to Watts(W). For accurate sizing, use the watt
rating of the equipment to determine the correct UPS and runtime. If the watt rating is unavailable use the Amp (A) rating and multiply by the voltage to obtain VA. For the most recent sizing information, please
consult the Size-UPS section of APC’s website at www.apc.com/sizing.
Available in tower and rack-optimized form factors. APC’s Smart-UPS XL is ideal for mis-
sion-critical applications where long term runtimes are essential. Voice-over-IP (VoIP) gate-
ways, telephone PBXs, critical application servers and data communications links will ben-
efit from the added availability of the XL models with additional battery packs.
Tower Units Rack-mount Units
New!
New!
New!
New!
New!
SPECIFICATION SUA750XLI SUA1000XLI SU2200XLINET SU1400RMXLI3U SU2200RMXLINET SU2200RMXLI3U SU3000RMXLI3U SU5000RMXLI5U
PowerChute Support for Windows Server 2003/2000/NT 4.0, Novell Netware, Red Hat Linux, SuSE Linux, Turbolinux and Sun Solaris
Business Edition 5 Node Version
Number of SmartSlot Bays 1 2
Input Line Cord (1.8m line cord)) IEC320 C14 IEC320 C20 IEC320 C14 IEC320 C20 Hardwire
Output Receptacle 8 C13 & 2 jumpers 8 C13 & 1 C19 8 C13 & 1 C19 plus 3 jumpers
Maximum Dimensions (H x W x D) 216 x 170 x 439mm 432 x 192 x 546mm 130 x 432 x 394mm 222 x 483 x 451 mm 133 x 483 x 660mm 222 x 483 x 451 mm
Net Weight 24.1 kg 27.3 kg 54.9 kg 31.8 kg 56.4 kg 56.4 kg 56.4 kg 93.2 kg
Shipping Weight 26.4 kg 29.4 kg 63.6 kg 38.6 kg 65 kg 63.2 kg 63.2 kg 102.3 kg
Replacement Battery Cartridge RBC 7 RBC11 RBC 25 RBC 11 RBC 27 (2) RBC12
Service level SB12 SB13 SB12 SB12 SB13 SB14
OPERATION
SUA750XLI SUA1000XLI SU2200XLINET SU1400RMXLI3U SU2200RMXLINET SU2200RMXLI3U SU3000RMXLI3U SU5000MXLI5U
Nominal Input Voltage 230 Vac, single phase, 50 or 60 Hz (auto-selectable)
Transfer Time (typical) 2 milliseconds, includes detection time
AVR Boost/Trim 30%/12% 12% / 12%
Default Input Voltage Range 174-286 Vac 174-286 Vac
Max input voltage adjustable range
for mains without battery discharge
1
168-302 Vac 168-302 Vac
Output Voltage Range 208-253 Vac 196-253 Vac
Capacity (Volt-Amps, Watts) 750, 600 1000, 800 2200, 1600 1400, 1050 2200, 1600 2200, 1750 3000, 2400 5000, 4000
Surge energy rating,
peak current capability 320 Joules
480 Joules, 6.5kA
Normal, common mode clamping
response time 0 ns, <5ns typical
Normal mode surge voltage let
through (IEEE 587 Cat. A 6kV test) <0.3% of peak typical
Batteries Maintenance-free sealed Lead-Acid battery with a 3-6 year typical lifetime: leakproof
Recharge time to 90% 3 Hours
Ambient Operation 3,000 m max. elevation, 0-95% humidity non-condensing; 0-40 deg C
Storage Conditions 15,000 m max.elevation; -15 to 45 deg C
Audible noise at 1 meter <42 dBA <53 dBA <45 dBA <53 dBA
BTUs/hr. 100 120 305 155 275 375 375 430
TYPICAL RUNTIME IN MINUTES
2
Load SUA750XLI SUA1000XLI SU2200XLINET SU1400RMXLI3U SU2200RMXLINET SU2200RMXLI3U SU3000RMXLI3U SU5000RMXLI5U
Watts
2
VA
300 420 51 51 122 55 122 127 127 382
600 840 17 17 52 19 52 56 56 98
800 1120 n/a 10 34 11 34 37 37 69
1400 1960 n/a n/a 13 n/a 13 14 14 31
2000 2800 n/a n/a n/a n/a n/a n/a 7 17
3000 4200 n/a n/a n/a n/a n/a n/a n/a 8
Uses Additional Battery Pack(s) SUA24XLBP SUA24XLBP SU48XLBP SU24RMXLBP2U SU48RMXLBP SU48R3XLBP SU48R3XLBP SU48R3XLBP
Ultra Extended Runtime Battery Pack UXBP24 UXBP24 UXBP48 n/a UXBP48 n/a n/a n/a
For extended runtimes refer to the table on page 9.
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12

Comments to this Manuals