Troubleshooting
26 Symmetra
®
PX 10-80 kW, 208V – Operation & Maintenance Guide – 990-1430 REV01
Module failure
Threshold Alarm
Display Message Meaning Corrective Action
Bad Battery Module A battery module has failed and
requires replacement.
Refer to Module Replacement Sec-
tion for procedures.
Bad Power Module A power module has failed and
requires replacement.
Refer to Module Replacement Sec-
tion for procedures.
Intelligence Module is
installed and failed
The Main Intelligence Module has
failed and requires replacement.
Replace the Main Intelligence Mod-
ule. Refer to Module Replacement
Section for procedures.
Redundant Intelligence
Module is installed and
failed
The Redundant Intelligence Module
has failed and requires replacement.
Replace the Redundant Intelligence
Module. Refer to Module Replace-
ment Section for procedures.
Display Message Meaning Corrective Action
Redundancy has been
lost
The Symmetra no longer detects
redundant power modules. Either
power module(s) have failed, or the
load has increased.
Option 1: If possible, install
additional power modules.
Option 2: Replace failed modules.
Refer to Module Replacement Section
for procedures.
Runtime is below alarm
threshold
Actual power module redundancy has
fallen below user-specified
redundancy alarm threshold. Either
power module(s) failed or the load
increased.
Option 1: If possible, install
additional power modules.
Option 2: Replace failed modules.
Refer to Module Replacement Section
for procedures.
Option 3: Decrease load or
reconfigure threshold.
Runtime is below alarm
threshold
The predicted runtime is lower than
the user-specified minimum runtime
alarm threshold. Either the battery
capacity has decreased, or the load
has increased
Option 1: Allow the battery modules
to recharge.
Option 2: If possible, increase the
number of battery modules.
Option 3: Reduce load or re-
configure threshold.
Load is above kW alarm
threshold
The load has exceeded the user
specified load alarm threshold
Reduce load or re-configure
threshold.