990-2283 Smart-UPS® VT 10-40kVA 400V Site Preparation and Installation Manual 27
System-Electrical Information
WARNING!
All electrical power and power control wiring must be installed by a qualified
electrician, and must comply with local and national regulations for maximum power
rating.
UPS ratings (380V)
10kVA
8kW
15kVA
12kW
20kVA
16kW
30kVA
24 kW
40kVA
32kW
Input voltage (V)/per phase 3x380/
220V
3x380/
220V
3x380/
220V
3x380/
220V
3x380/
220V
Input current (nominal) (A) 13.0 19.4 26.0 38.6 51.7
Maximum input current (continuous, at minimum
mains voltage)/per phase
14.3 21.5 28.6 42.5 56.8
Input current protection for mains source or single
mains supply (external to UPS, not supplied) (A)
3x20 3x35 3x50 3x63 3x80
Input current protection for bypass source in dual
mains configuration (external to UPS, not supplied) (A)
20 35 50 63 80
Input frequency (Hz) range 40-70 40-70 40-70 40-70 40-70
Output voltage (on line). (V)
Minimum and maximum values (+/- 1%)
3x380/
220V
3x380/
220V
3x380/
220V
3x380/
220V
3x380/
220V
Output current (nominal) (A) 15.2 22.8 30.4 45.6 60.8
Maximum output current
(in bypass only at 110% overload per phase)
16.7 25.1 35.4 50.1 66.9
Bypass input current (A)
(in bypass only at 110% overload, per phase)
16.7 25.1 35.4 50.1 66.9
Neutral output current (with 100% switch mode load)
(A)
25.0 37.5 50.0 75.0 100.0
Output current protection (external to UPS, not
supplied) (A)
20 35 35 63 80
Output frequency range (Hz) 50/60 50/60 50/60 50/60 50/60
DC overcurrent protection and disconnect switch for
external safety: (A)
DC voltage rating of the battery supply
Maximum available battery short-circuit current.
22
+/- 192
10kA
33
+/- 192
10kA
44
+/- 192
10kA
66
+/- 192
10kA
88
+/- 192
10kA