11MGE™ Galaxy™ 3500 10-40 kVA 380/400/415 V, 10-30 kVA 208/220 V Battery Installation
Run the Cables
Connect Power in Installations with Busbars
Warning: Before carrying out the steps below, you must follow the Total Power Off
procedure in the Operation Manual.
Install isolators
See “Specifications” on page 23 for torque specification.
The isolators separate the baying kit busbar from the six vertical busbars in each XR Battery Enclosure,
and the (+), N, and (-) busbars in the UPS. This is how the isolators are fitted to their busbar:
1. Guide the isolator busbar
through the adjacent side
panels.
2. Position the isolators
across the vertical
busbars (N in this
example) and then fasten
the isolator busbar by
using the provided M5
Torx screws.
3. Secure the isolator to its
busbar with cable ties.
+
N
+
N
N