23MGE™ Galaxy™ 3500 10-40 kVA 380/400/415 V, 10-30 kVA 208/220 V Battery Installation
Specifications
Battery voltage and current
Recommended cable sizes
Note: Power terminal lug diameter: minimum 6 mm (0.2 in).
Torque value: 45 lbf-in/7 Nm.
Note: Use Molex lug type or equivalent, and follow the manufacturers specifications.
EPO requirements
Torque specification
Torque specification: Isolators: M5 7 Nm (45 lbf-in).
XR Battery Enclosure 30 kVA 40 kVA
Battery voltage (nominal) ± 192 VDC ± 192 VDC
Battery current (at full load) 69.4 A at ± 192 V 87.9A at ± 192V
Max. current (at end of discharge) 86.6 A at ± 154 V 110.1A at ± 154V
If the XR Battery Enclosure is customer-supplied, please refer
to product-specific data.
North America Europe, Middle East, Asia
208/220 V 380/400/415 V
BAT+, N, BAT- 35mm
2
1 AWG
167º F (75º C) copper wire
BAT+, N, BAT- 50 mm
2
75º C
(167º F) copper wire
SELV voltage 24 VDC
Current: 1500 mA