MGE™ Galaxy™ 3500 10-40 kVA 380/400/415 V, 10-30 kVA 208/220 V Battery Installation12
Install busbars
523 mm (20.59 in) UPS System with the UPS placed to the left (seen from the front).
1. Install the following baying kit busbars between the UPS and XR1:
880-1607 between the vertical busbar N on the UPS and busbar 4 on XR1
880-1606 between the vertical busbar (+) on the UPS and busbar 1 on XR1
880-1605 between busbar (-) on the UPS and busbar 6 on XR1
2. Install the following baying kit busbars between the two XR Battery Enclosures:
880-0926 between the vertical busbar 3 on XR1 and busbar 4 on XR2
880-0940 between the vertical busbar 2 on XR1 and busbar 1 on XR2
880-0941 between the vertical busbar 5 on XR1 and busbar 6 on XR2
N
+
XR2
XR1
UPS