MX06 Power Plant User’s Manual Page 18
4.2. System Management
A single plug-in circuit card provides the control, display and user interface functions for the
MX06. Features include the following:
Control Functions
a) The Control Module is “hot-pluggable”.
b) The plant voltage can be adjusted through the use of a front panel accessible
potentiometer. The power plant will operate without the Control Module at a factory pre-
set voltage of approximately 54.5 VDC.
c) Automatic temperature compensation is available when a temperature probe is plugged
into the rear panel.
d) Motorized circuit breaker control, allowing for battery disconnect and reconnect at specific
voltage levels.
Alarm Functions
Rectifier and plant discrete alarm points are monitored along with the plant voltage:
e) Rectifier input healthy
f) Rectifier output healthy (1-of-N, 2-of-N)
g) GMT fuse trip
h) Battery breaker trip
i) Voltage level: High voltage, low voltage, very low voltage.
j) User-defined alarm inputs
Displays
Front panel LEDs provide the following indications:
k) VOLTAGE GOOD (Green): Output voltage between the low voltage and high voltage
thresholds (50V dc to 57V dc).
l) MAJOR (Red): Major alarm condition
m) MINOR (Yellow): Minor alarm condition
n) LOW V (Yellow): Low Voltage (50V dc)
o) VERY LOW V (Red): Very Low Voltage. Imminent disconnect of battery if LVD in use
(44V dc)
User Outputs
Alarm outputs, Form C relay contacts:
p) Major Alarm
q) Minor Alarm
r) Very Low Voltage Alarm
s) Motorized Relay control connections: Used for battery over current disconnect and
battery low voltage disconnect.