MX06 Power Plant User’s Manual Page 25
MX06-100 Programmable Alarms
The GMT alarm, and the battery circuit breaker alarm can each be programmed to either
MAJOR or MINOR alarm priority. A three-pin jumper header is used for each alarm in the
manner shown in Figure 13. Figure 12 locates the jumpers on the PC board. If no jumper is in
place, then no alarm will be reported. Do not touch any jumpers, other than J6 and J9, as they
are factory set for the configuration that you order.
Figure 5.4-2 MX06-100 Jumper Programming
Alarm
Jumper
Designator
Major
Setting
Minor
Setting
No Alarm
Output
Factory
Setting
GMT
Alarm
J9
Pins
2 and 3
Pins
1 and 2
No
Jumper
Major
Battery
Breaker
Alarm
J6
Pins
2 and 3
Pins
1 and 2
No
Jumper
Major
Figure 5.4-3 MX06-100 Alarm Jumpers
MX06-100 Temperature Probe Selection
Temperature compensation can be configured for either a Fahrenheit or Celsius probe by the
use of configuration jumpers on pin header J3 shown in Figure 5.4-1. The MX06-100 is factory
set for Fahrenheit operation, with jumpers on all position of J3.
MAJOR
1 2 3
MINOR
1 2 3