Purpose and benefits of outlet groups
By using groups of synchronized outlets on Switched Rack PDUs, you can ensure that
outlets turn on, turn off, and reboot in a synchronized manner. Synchronizing control
group actions through outlet groups provides the following benefits.
Synchronized shutdown and startup of the power supplies of dual-corded servers
prevents erroneous reporting of power supply failures during a planned system
shutdown or reboot.
Synchronizing outlets by using outlet groups provides more precise shutdown and
restart timing than relying on the delay periods of individual outlets.