USER’S GUIDE
Switched Rack PDU
5
Recover From a Lost Password
You can use a local computer, a computer that connects to the Rack PDU or other
device through the serial port, to access the control console.
1. Select a serial port at the local computer, and disable any service that uses that
port.
2. Connect the serial cable (APC part number 940-0144A) to the selected port on the
computer and to the configuration port at the Rack PDU.
3. Run a terminal program (such as HyperTerminal
®
) and configure the selected port
for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.
4. Press
ENTER, repeatedly if necessary, to display the User Name prompt. If you are
unable to display the User Name prompt, verify the following:
The serial port is not in use by another application.
The terminal settings are correct as specified in step 3.
The correct cable is being used as specified in step 2.
5. Press the Reset button. The Status LED will flash alternately orange and green.
Press the Reset button a second time immediately while the LED is flashing to reset
the user name and password to their defaults temporarily.
6. Press
ENTER as many times as necessary to redisplay the User Name prompt, then
use the default, apc, for the user name and password. (If you take longer than 30
seconds to log on after the User Name prompt is redisplayed, you must repeat step
5 and log on again.)
To set User Name and Password values for Administrator, Device
User, and Read-Only Users accounts, see Setting user access
(Administration>Security>Local Users>options).
You must use the Web interface to configure values for the
Read-Only User and Outlet User.