Smart-UPS® VT 10-40 kVA 380/400/415 V - 208/220 V - 200/208 V Installation in Parallel14
Breaker sizes 380/400/415 V
Q3 in capacity systems.
Q4 in capacity systems.
Q3 in redundant systems (n+1).
Q4 in redundant systems (n+1).
Q1 and Q5 in capacity and redundant systems.
Rating in kVA (380/400/415 V)
Units in parallel 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
2 35 A 50 A 63 A 100 A 125 A
3 50 A 80 A 100 A 160 A 200 A
4 63 A 100 A 125 A 200 A 250 A
Rating in kVA (380/400/415 V)
Units in parallel 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
2 35 A 50 A 63 A 100 A 125 A
3 50 A 80 A 100 A 160 A 200 A
4 63 A 100 A 125 A 200 A 250 A
Rating in kVA (380/400/415 V)
Units in parallel 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
2 16 A 25 A 35 A 50 A 63 A
3 35 A 50 A 63 A 100 A 125 A
4 50 A 80 A 100 A 160 A 200 A
Rating in kVA (380/400/415 V)
Units in parallel 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
2 16 A 25 A 35 A 50 A 63 A
3 35 A 50 A 63 A 100 A 125 A
4 50 A 80 A 100 A 160 A 200 A
Rating in kVA (380/400/415 V)
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Bypass overcurrent
protection Q1
16 A 25 A 35 A 50 A 63 A
Bypass overcurrent
protection Q5
16 A 25 A 35 A 50 A 63 A