3Smart-UPS® VT 10-40 kVA 380/400/415 V - 208/220 V - 200/208 V Installation in Parallel
Interconnection Plates
Note: The enclosures in a parallel system can be kept apart, or they can be assembled with
interconnection plates (SUVTOPT011 APC Smart-UPS VT Parallel Operation Baying Kit). If
the enclosures are kept apart the communication cables can be run in conduits (if applicable).
Note: When enclosures are assembled with interconnection plates and bolted together, the
PBus cables can be routed inside the enclosures and then only the ABus cable has to be run in a
conduit (if applicable).
Note: If cables must run in conduits according to local regulations please make sure that all
cables outside the UPSs are run in conduits.
Remove the front panel and the top cover
Turn the screw to the right to the unlocked position.
Lift the front panel upwards to free it from the enclosure
frame.
Loosen the six screws of the top cover (four at the
xxfront and two at the back).
Lift up from the back and push forward to free the
xxcover.
Leave the cover unattached on top of the UPS.
Note: Remove the battery compartment cover (only applicable to Japanese systems).