APC ACRC103 Specifications Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
17InRow Half-Rack RC Installation
Connect piping
See “Piping Diagrams,” beginning on page 8, for recommended valve, flexible adapter, and
strainer installation locations.
1. Route all piping
to the InRow RC in compliance with all local and national codes.
Note: Circuit setters are required to regulate the flow of chilled water to each piece of
equipment. When a CDU is used in conjunction with the equipment, circuit setters are
not required, as the CDU provides the flow-regulating function.
Note: The figure shows a top piping installation with a PEX fitting. Bottom piping
installations or rigid piping fittings are handled similarly.
2. Disassemble the union on the entering or exiting water line:
a. Remove the nut
from the body
.
b. Remove the disc
and gasket
. Save the gasket.
c. The disc
prevents water flow through the union.
Discard the disc
.
3. Repeat step 2 for the union on the other water line.
4. Assemble the union on the entering or exiting water line:
a. Use thread sealant and thread sealing tape in accordance
with local and national codes.
b. Slide the nut
onto the fitting
.
c. Seat the gasket
into the body
.
d. Tighten the body
onto the nut
, using a properly-
sized open end wrench.
5. Repeat steps 1 through 4 for the union on the other water line.
Condensate pump. The pump is factory-wired and piped
internally to the lower condensate pan. The pump is capable of
moving liquid a maximum of 15.2 m (50 ft), including
a
maximum lift of 4.9 m (16 ft). For example, if your lift is 3 m
(10 ft), you have 12.2 m (40 ft) of usable run. The pump also
uses an on-board condensate high level float switch, which is
wired into the InRow RC alarm input for local
and remote alarm capabilities.
na2239a
na1575a
Warning: Do not exceed the lift or the run
length of the drain system.