InRoom CW/DX – Operating Instructions16
2.5 Cooling water circuit (G, GCW, GE)
In G- and GCW units, the cooling water circuit contains a plate condenser as the interface to the refrigerant
circuit and two valves for fi lling and draining.
In GE units the water circuit contains additionally a direct cooling coil, two 2-way ball valves and a tempe-
rature sensor at the water inlet.
The distribution of the water fl ow through the free cooling coil and the condenser is taken on by two ball
valves controlled by the controller (one for the condenser and one for the free cooling coil). The ball valve
control factor in the condenser circuit is the condenser pressure on the refrigerant side. T he ball valve control
factor for the GE-coil is the temperature at the water inlet.
2.6 Chilled water circuit (ACW, GCW)
The chilled water circuit consists of a direct cooling coil, a 3-way valve, by which the cooling capacity is
controlled, and fi lling and vent valves. The 3-way valve is controlled by the incorporated controller.
Component protection
Compressor
The compressor is equipped with an internal high pressure protection which opens a bypass in case of high
pressure, so that an internal pressure compensation takes place. Refer to "Safety Switches" on page 15 for
more information.
Fan
The EC fan control contains safety elements which protect the fan in case of phase failure, voltage fl uctuation
and excessive current. If the voltage in one or more phases drops for 5 seconds or longer below 290 V, the
fan is switched off and an airfl ow alarm is generated. In consequence of the alarm, the compressor and, if
existant, the reheat and humidifi er are also switched off.
After the supply voltage returns the airfl ow alarm must be manually reset in order to restart the cooling
unit.
In areas with unstable electrical supply networks, the option "three phase control" should be chosen. With
this option the cooling unit starts automatically after the return of the supply voltage.