InRoom CW/DX – Operating Instructions
h
60
(2.36)
330
(13.0)
>4 inch
(>10 cm)
48
Unit limit
Possible installation at the
customer side: funnel
Siphon installation
Ensure that there is a suffi cient height difference between the fan pan and the upper bow of the siphon or the
highest part of the drain tube, in order to avoid a water column in the drain siphon caused by the pressure
in the suction area of the cooling unit, which prevents the draining of the condensate water.
Connect the condensate water drains to the local waste water system.
Note:
Comply with regulations in accordance with state and local codes.
Example: Static pressure in the suction area :
–1 in.w.g. (–250Pa)
h = p / (ρ • g)
h = –250Pa / (1000kg/m³ • 10m/s²)
h = –1 inch (h = –2.5 cm)
If the height h is less than 1 inch (2.5 cm) with a
pressure of 1 in.w.g. (250 Pa) in the suction area,
a water column rests in the drain. The water is
not transported and fi lls the fan pan. This water
can be drawn down in the fan or can be drained
out of the unit if the pan is full.
6.3.4 Condensate drain connection
The condensate drain connection (3/4 in) is
located in the middle section, right bottom.
The siphon is delivered with the unit and has
to be mounted in the raised fl oor on site after
the cooling unit has been installed.