APC INROOM ACPSC3000 Operations Instructions Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
InRoom CW/DX – Operating Instructions
52
Controller, Start/stop-key
• Adjust the return air temperature at the controller.
• Start the cooling unit by pressing the Start/Stop-key on the controller.
• After 20 minutes of operation, check whether bubbles are visible in the sight glass of the liquid line. If
this is the case, refrigerant might have escaped by a leak. Check the circuit for leaks, eliminate these
and charge the system with additional R407C refrigerant, if necessary. See "Maintenance", beginning
on page 76, for additional information.
• Check the oil level at the compressor.
The oil level should be between the lower quarter and the middle
of the sight glass.
• Check the current consumption of the compressors and the fans,
comparing it with the values of the technical data.
• Teach the operational staff how to use the controller (refer to the
controller manual).
Compressor sight glass
Page view 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 79 80

Comments to this Manuals

No comments