InRoom CW/DX – Operating Instructions
Baugröße 1 2 3 4 5
Befeuchtungsleistung
lb/h
17.6 33
Befeuchtungsleistung [kg/h] (lb/h)
Nennstrom [A] Nennleistung [kW]
8 (17.6) 7.5 6,0
15 (33) 14.1 11,25
Befeuchtungsleistung [kg/h] (lb/h)
Nennstrom [A] Nennleistung [kW]
8 (17.6) 16.7 6,0
15 (33) 11,25
54
The steam humidifi er is optional for your cooling unit. It is installed complete and integrated within the function
and method of operation of the cooling unit. Details concerning the connection assignment for the power
supply can be found in the electrical diagrams in the appendix.
Caution:
We recommend the installation of an Aqua-stop valve in the water supply of the humidifi er.
In addition to this, the room, in which the cooling unit with the humidifi er is installed, should
be equipped with a water detection system.
9.1.1 Description
The humidifi er uses potable water for the production of steam. The conductivity of the water should be within
the range of minimal 760 to maximal 3175 µS/inch. The water is converted directly into steam by means
of electrical energy in a steam cylinder with electrode heating. The steam is introduced into the airfl ow via
the steam throttle.
Due to the evaporation the water level in the cylinder falls. The current consumption is reduced, as the elec-
trodes are then immersed less in the water, as water level sinks the mineral concentration in the cylinder
increases, as the minerals do not evaporate. The humidifying control keeps the current between two limit
values (IN+10%, IN-5%). When the lower limit value is reached, the inlet valve opens. Now fresh water is mixed
with residual water, which has a high mineral concentration. After several evaporation and fi lling cycles, the
mineral concentration is so high, that the current reduction due to evaporation and falling water level takes
place quite rapidly. When a limit value of current reduction is exceeded, the drain valve is opened. When the
lower current limit value is reached, the cylinder is completely drained.
NOTE: Th e fi lling phase is automatically interrupted if the sensor electrode is contacted due to the high
water level in the steam cylinder. This may happen in the start-up phase with a new steam cylinder.
9.1.2 Technical data
Two different sizes of humidifi ers are available in the InRoom CRAC. Yo u can see which humidifi er is installed
in your unit from the following table.
9. Options
9.1 Steam humidifi er
Cabinet size
Humidifying capacity
lb/h
460V / 3ph / 60Hz
230V / 3ph / 60Hz
Humidifying capacity[kg/h] (lb/h)
Nominal current [A] Nominal power [kW]
Humidifying capacity[kg/h] (lb/h)
Nominal current [A] Nominal power [kW]