APC AIS 3000 User Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
AIS® 3000 10-30kVA, 208V, Site Preparation and Installation Manual – 990-1957 17
Operating Environment
Operating conditions
Heat dissipation
Audible noise
Install the UPS in an indoor, temperature-controlled area, free of conductive
contaminants.
Temperature
Range:
32° to 104°F /
0° to 40°C
Keep Ventilated
Front-to-Rear
Airflow (see
space
considerations)
Relative
Humidity: <95%
Non-condensing
No Conductive
Dust or
Corrosive
Fumes
Altitude derating table:
3000ft/914m: 100% load
4500ft/1371m: 95% load
6000ft/1828m: 91% load
8000ft/2438m: 86% load
10000ft/3048m: 82% load
UPS size BTU/hr at fully charged batteries
10kVA 1,774
15kVA 2,866
20kVA 3,624
30kVA 5,486
10-15kVA 20-30kVA
Audible noise at 100% load:
(measured 1.09yard/1m from the
UPS)
64dBA 67dBA
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 57 58

Comments to this Manuals

No comments