Smart-UPS Rear Panel
MADE IN USA (WEST KINGSTON, RI)
SU1400RMX L3U
XX0123456789
®
Computer Interface Port
Power management software and interface kits can be used with this UPS. Use only interface kits
supplied or approved by APC. If used, connect the interface cable to the 9-pin computer inter-
face port on the back panel of the UPS. Secure the connector’s screws to complete the connection.
TVSS Screw
The UPS features a transient voltage surge-suppression (TVSS) screw for connecting the ground
lead on surge suppression devices such as telephone and network line protectors. Refer to
Connect Power and Equipment to the UPS, page 10, for information.
Voltage Sensitivity
The UPS detects line voltage distortions such as spikes, notches, dips, and swells, as well as
distortions caused by operation with inexpensive fuel-powered generators. By default, the UPS
reacts to distortions by transferring to on-battery operation to protect the connected equipment.
Where power quality is poor, the UPS may frequently transfer to on-battery operation. If the
connected equipment can operate normally under such conditions, battery capacity and service life
may be conserved by reducing the sensitivity of the UPS.
To reduce UPS sensitivity, press the Sensitivity button on the rear panel. Use a pointed object
such as a pen to press the button. Press it once to set the UPS’s sensitivity to reduced. Press it
again to set the sensitivity to low. Press the button a third time to reset normal sensitivity. The
Sensitivity can also be changed through software.
normal
reduced
low
When the UPS is set to normal sensitivity, the LED is brightly lit.
When it is set to reduced sensitivity, the LED is dimly lit.
When it is set to low sensitivity, the LED is off.