13
English
10.3 Battery Replacement Procedure (280, 420 and 650 VA
models)
Note:Note:
Note:Note:
Note: Please read the cautions in section 10.1.
Battery replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and loads
on for the following procedure.
1. Lay the UPS on its left side. Remove the two screws holding on the battery door and
openopen
openopen
open the door.
Note:Note:
Note:Note:
Note: The battery door may need to be pulled away from the hinges somewhat to allow it to become
fully swung open.
2. Gently
pullpull
pullpull
pull out the battery by grasping the white tab.
3.
DisconnectDisconnect
DisconnectDisconnect
Disconnect the two wires connecting the battery to the UPS. Loosen the wires by gently wiggling them
while pulling straight back from the battery connector.
4.
ConnectConnect
ConnectConnect
Connect the new battery in place of the old.
Note:Note:
Note:Note:
Note: Small sparks at the battery connections are normal
during connection.
5.
RR
RR
R
ee
ee
e
placeplace
placeplace
place the new battery in the UPS. Use care to avoid pinching the wires.
6.
CloseClose
CloseClose
Close the battery compartment door and replace the screws.
7.
DisposeDispose
DisposeDispose
Dispose of the old battery properly at an appropriate recycling facility or return it to the supplier in the
packing material for the new battery. See the new battery instructions for more information.