Site Preparation – Operating Environment
990-1598B Smart-UP VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 15
Recommended phase-conductor sizes [AWG] for a 86°F (30°C) temperature
environment
)
EPO switch wiring
The UPS must be connected to either a dry contact or a 24VDC Emergency Power Off (EPO) switch.
UPS/AWG sizes
Mains input
[AWG]
AC output
[AWG]
DC input
[AWG], 75°C Wire
10 kVA 8 8 1
15 kVA 6 6 1
20 kVA 4 4 1
30 kVA 1 1 1
Note
Use Molex lug type or equivalent, and crimp to manufacturers specifications.
Cable Size
[AWG] Cable Lug Type Crimping Tool Die
Terminal Bolt
Diameter
12 YA12CL2TC38 MD7-34R W12CVT 0.2 in/6 mm
8 YA8CL2TC38 MD7-34R W8CVT 0.2 in/6 mm
6 YA6CL2TC38 MD7-34R W5CVT 0.2 in/6 mm
4 YA4CL2TC38 MD7-34R W4CVT 0.2 in/6 mm
1 YA1CL2TC38 MD7-34R W1CVT 0.2 in/6 mm
WARNING!
At 100% non-liniear load (EN50091-3 standard), the neutral shall be rated for 200%
phase current.
See “Pin connections J108 (for EPO wiring options)” on page 37