FullLoadHeatLossatNominalMains
WARNING:ThisisaClassAUPSproduct.Inadomesticenvironment,thisproduct
maycauseradiointerference,inwhichcase,theusermayberequiredtotakeadditional
measures.
208V:208V480V:208V600V:208VNotransformer
Fullloadheatloss
(kW)
3.23.12.61.5
BTU/hour10,91910,5788,8725,118
Batteries
BatteryInput
Nom.voltage(VDC)2x192
I
Nom
discharge
1
282
I
Max
discharge
2
351
Minimumdischargevoltage1.6-1.75V/cell(automatic,dependingonload)
1
Nominalbatterydischargecurrentbasedonratedloadandnominalbatteryvoltage(2.0V/cell)
2
Maximumbatterydischargecurrentbasedonratedloadattheendofthedischarge(1.6V/cell)
990–3659C-001
SymmetraPX100kW208V