Specifications
Caution:Allelectricalpowerandpowercontrolwiringmustbeinstalledbyaqualified
electrician,andmustcomplywithlocalandnationalregulationsformaximumpowerrating.
Note:Allcurrentvaluesarebasedona100kWmaximumconfigurationoftheUPS.
SpecificationsforInstallationswithoutPDU
ACInput
208VUPSonly
Connectiontype,singlefeed4-wire(3PH+N+G)
Connectiontype,dualfeedMainsinput:3wire(3PH+G),BypassMainsinput:
4-wire(3PH+N+G)
Nom.inputfrequency(Hz)
1
60
Nom.inputcurrent(A)
2
302
Max.inputcurrent(A)
3
332
Inputcurrentlimit(A)
4
360
Nom.bypassinputcurrent(A)278
Maximumavailablefaultcurrent(kA)
5
30
1
Inputfrequency(Hz)40-70with10Hz/secslewrate.
2
Inputcurrentbasedonnominalvoltageandratedload,batteriesfullycharged.
3
Inputcurrentbasedonfullbatteryrecharg,nominalvoltageandratedload.
4
Currentlimitationthroughelectroniccurrentlimitingisbasedonfullratedloadandlimitedbatteryrechargefrom
-10%to-15%inputvoltage.
5
ThemaximumavailablefaultcurrentwasnotevaluatedbyUnderwritersLaboratories.
ACOutput
208VUPSonly
Connectiontype4-wire(3PH+N+G)or3wire(3PH+G)
Nominaloutputcurrent(A)278
2
SymmetraPX100kW208V
990–3659C-001