EmergencyPowerOff(EPO)Switch
Note:EPOswitchwiringmustcomplywithlocalandnationalCodewiringrules.Review
theplannedEPOinstallationandoperationwiththelocalAuthorityHavingJurisdiction
(AHJ)beforeproceedingwiththefinalinstallation.
Note:Connectioninspringpushconnectorshastobemadebysinglesolidcoreormultiple
strandedwireterminatedwithacableferule.
Note:TheUPScancontinuetosupplyACpowertotheloaduntilallACandDCsources
havebeendisconnected.Thebuilt-inEPOfunctiondisconnectsonlytheinternalDC
sources.Tofullyde-energizeallACandDCpowerintheUPS,theupstreamcircuitbreaker
protectingtheinputfeedercircuittotheUPSmustbeprovided(byothers)withatripping
mechanism(usuallyashunttrip).Thestatusoftheupstreamexternalcircuitbreakercanbe
monitoredviathecircuitbreaker’saux.switchattheMaintenanceBypassPanelinterface.
Note:Theremotedisconnectcontrol(EPOstation)mustprovideadrycontactsignal
(normallyopenornormallyclosed)totheUPSandsimultaneouslyprovideasignaltothe
tripmechanismontheupstreamexternalcircuitbreakerfeedingtheUPS.
TheUPScanbeconnectedtoeitheradrycontactoranexternal24VDCsource.
TheEPOcircuitisconsideredClass2andSELV(SafetyExtraLowvoltage).ASELVcircuitisisolated
fromprimarycircuitrythroughanisolatingtransformeranddesignedsothatundernormalconditions,
thevoltageislimitedto42.4Vacpeakor60VDC.SELVandClass2circuitsmustbeisolatedfromall
primarycircuitry.DonotconnectanycircuittotheEPOterminalblockunlessitcanbeconfirmedthat
thecircuitisSELVorClass2.
InstallationsintheUS:
•CL2Class2cableforgeneralpurposeuse
•CL2Plenumcableforuseinaverticalshaftorfrom
floortofloor
•CL2RRacercableforuseindwellingsandraceways
•CL2XLimitedusecablefordwellingsandraceways
InstallationsinCanada:
•CL2RCertified,typeELC(Extra-Low-Voltage
ControlCable)
•CL2XCertified,typeELC(Extra-Low-Voltage
ControlCable)
990–3659C-001