Air Flow <n> ft/min
Settings for sensors that
measure air movement as feet
per minute.
Note: Sensors that use a
different measurement, such as
cubic feet per minute (CFM) will
be displayed under the Other
Numeric Sensors option.
Audio Relative number (0 - 100)
Settings for sensors that
measure the volume of sound.
Current (Amps) Amps (0.0 - 100.0)
Settings for sensors that
measure current as total
amperage (amps).
Dew Point °F (-40.0 - 122.0)/ °C (4.5 - 50.0)
Settings for sensors that
measure dew point as degrees
Fahrenheit (°F) or Celsius (°C).
Humidity % (0 - 95)
Settings for sensors that
measure relative humidity as a
percentage (%).
Other Numeric Settings Varied
Settings for sensors that
measure numeric settings not
reported for other Alert
Thresholds options.
Power (VA) VA
Settings for sensors that
measure power as total Volt-
amperes (VA).
Note: Sensors that measure
power as a percentage of VA
will be displayed under the
Other Numeric Sensors
option.
Power (Watts) W
Settings for sensors that
measure power as total watts
(W).
Temperature °F (-40.0 - 122.0)/ °C (4.5 - 50.0)
Settings for sensors that
measure temperature as
degrees Fahrenheit (°F) or
Celsius (°C).
Voltage V
Settings for sensors that
measure either AC or DC
voltage as total volts (V).
Numerical threshold types
Setting Description
Minimum Value Threshold
An alarm occurs when the sensor's value is
below the Minimum setting.
Maximum Value Threshold
An alarm occurs when the sensor's value is
above the Maximum setting.
Range Threshold
An alarm occurs when the sensor's value is
outside the range defined by the Minimum and
Maximum settings.