Installation and Quick Start 15
Quick Configuration
Local access to
the control
console
You can use a computer connected to the serial port on the
front of the Management Card to access the control console.
1. Select a serial port at the local computer, and disable any
service that uses that port.
2. Use the configuration cable to connect the selected port
to the serial port on the front panel of the Management
Card. Use either 940-0024C, the 6-ft cable that came
with your UPS, or AP9804 (990-1524), the 15-ft cable
available from APC.
3. Run a terminal program (such as HyperTerminal) and
configure the selected port for 2400 bps, 8 data bits, no
parity, 1 stop bit, and no flow control. Save the changes.
4. Press
ENTER to display the User Name prompt.
5. Use apc for the user name and password.
Remote access
to the control
console
From any computer on the same subnet as the Management
Card, you can use ARP and Ping to assign an IP address to a
Management Card, and then use Telnet to access its control
console and configure the other TCP/IP settings.
1. Use the Management Card’s MAC address in the ARP
command to define the IP address.
For example, to define 156.205.14.141 as the IP address
of a Management Card with 00 c0 b7 63 9f 67 as its
MAC address., use one of the following commands:
Windows command format:
arp -s 156.205.14.141 00-c0-b7-63-9f-67
LINUX command format:
arp -s 156.205.14.141 00:c0:b7:63:9f:67
See “Control console” on page 16 to finish the
configuration.
Note
After a Management Card has its IP address
configured, you can use Telnet, without first using
ARP and Ping, to access that Management Card.
Note
For the MAC address, look on the bottom of
the Management Card or on the Quality
Assurance slip included in the package.