APC Metered Rack User's Guide Page 33

  • Download
  • Add to my manuals
  • Print
  • Page
    / 39
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 32
Command Reference: Switched Rack PDU
Command Line Interface (CLI) User’s Guide 29
pducoldstartdelay
Syntax (to read the cold-start delay):
pducoldstartdelay
Syntax (to set the cold-start delay):
pducoldstartdelay {time|never}
Description: Set or read the PDU cold-start delay
(the time that the Switched Rack PDU delays
applying power to the outlets after AC power has
been applied to the Switched Rack PDU).
Access: Administrator and device manager
(device-only user)
Parameters:
Output format, reading the cold start delay:
OK
PDU_name: PDU coldstart delay is time seconds.
Output format, setting the cold start delay:
OK
PDU_name: Setting PDU coldstart delay to time
seconds.
Error Messages: E101, E104
power
Syntax:
power
Description: Reads the total power usage of the
Switched Rack PDU in watts and volt-amps.
Parameters: None.
Access: All three user types with access to the
CLI.
Output Format:
OK
power_in_volt-ampsVA
power_in_wattsW
Error Message: 101
time The cold-start delay in seconds to set for the
Switched Rack PDU. Allowed values are 0
through 300.
never Sets the Switched Rack PDU to keep its
outlets turned off after power is applied until
the outlets are explicitly turned on by the on
command.
Page view 32