APC SBP User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 9
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
Service Bypass Panel 1500/2200/3000 Rack-Mount Series User Manual 5
Hardwire the SBP
Hardwiring must be performed by a qualified electrician.
Adhere to all national and local electrical codes.
SBP3000RMHW model
1. Switch the utility circuit breaker off.
2. Remove the two screws that secure each access
panel to the SBP.
3. Secure the utility power cables,
Line1, Line2/Neutral, Ground to the input
terminal block.
Apply torque of 0.8 Nm (7 lb-in).
4. Secure the equipment power cables,
Line1, Line2/Neutral, Ground to the output
terminal block.
Apply torque of 0.8 Nm (7 lb-in).
5. Secure the access panels with the screws
removed in step2.
6. Connect the input and output cables on the UPS
to the SBP input and
output receptacles.
7. Switch the utility breaker on.
8. Turn on the UPS.
9. Turn the SBP Bypass/UPS switch to the UPS
position.
Connect power and equipment to the SBP
1500RM/1500RMI/2200RM/3000RM/3000RMI models
1. Connect the power cord from the UPS to the UPS input receptacle on the SBP.
2. 1500RM/2200RM/3000RM models: Connect the short UPS output power cord on the SBP to the output receptacle
on the UPS.
1500RMI/3000RMI models: Use the supplied power cord to connect the SBP output power receptacle to the UPS
output power receptacle.
3. 1500RM/2200RM/3000RM models: Connect the long SBP utility power cord to utility power.
1500RMI/3000RMI models: Connect the supplied power cord to the SBP input power receptacle and to utility
power.
4. Connect equipment to the equipment outlets on the SBP.
5. Turn on the UPS
6. Turn the SBP Bypass/UPS switch to the UPS position.
su0505a
L1
L2/N
L1
L2/N
su0544a
Output
Input