Page view 6
Temperature/Humidity Module 3
Front and Rear Panel
Components
Front panel
Use the toolless mounting pegs on the front panel
of the TH Module to install it in an APC rack or
enclosure without using any U-spaces.
Rear panel
T/H Expansion
Module
aem0051a
Item Description
24 VDC Input Provides supplemental power for
high-current load configurations.
User Inputs Connect four sensor devices.
Supports the following:
Dry contacts
0-5 V digital signals
See the Environmental Manager:
TH Module Users Guide, available
on the included Utility CD or on the
APC Web site (www.apc.com), for
configuration information
Voltage Output Provides 12 VDC or 24 VDC (75
mA) to a connected device.
Alarm Beacon
port
Connect an alarm beacon (AP9324).
A-Link ports Connect to the expansion bus for
cascading APC TH Modules
(AP9341) to a Main Module
(AP9340). The bus provides
communications and power to the
TH Modules using standard CAT5
cabling with straight-through
wiring.
Identifier #
LED display
View the identifier number, or
change it by pressing the arrow
button.
Sensor ports Connect a combination of up to six
temperature or temperature/
humidity sensors (AP9335T or
AP9335TH).