Smart-UPS should be identical tower, rack-mount, extended run or rack-mount extended models where applicable
2
Has (2) NEMA 5-15 receptacles for load(s).
3
Has (1) NEMA L5-30 receptacle for load(s)
In this application, a Redundant Switch is used with two identical
Smart-UPS and PowerChute plus. In networking environments where
redundant drives, processors, and power supplies are commonplace,
mirrored power protection configuration should be a major considera-
tion. Protection: Both Smart-UPS will provide continuous EMI/RFI fil-
tering and surge suppression. Battery backup is available in case of a
primary or redundant AC source failure. In case of a severe power
event, the redundant Smart-UPS will continue to support the load and
also provide graceful shutdown to Windows NT, Novell and Solaris
based operating systems. Power monitoring and management is avail-
able with PowerChute plus for Windows NT, NetWare, and Solaris-
based operating systems software and APC accessories. In this con-
figuration, the Redundant Switch also has an Emergency Power Off
(EPO) connector which allows the Smart-UPS to be switched off by a
remotely operated EPO control. Such a configuration is common in
computer rooms and laboratories where, for safety reasons, power to
the loads may need to be disconnected.
Redundant
Switch
= Communications
= Power
AC Source “A”
AC Source “B”
Best:
Server
Smart-UPS ‘B’
Smart-UPS ‘A
Note: Smart-UPS 2200 VA and 3000 VA units used with Redundant
Switch models SU042-1 and SU042-2 require an additional backplate.
For each UPS, order the appropriate backplate, as listed below:
Tower units: SU027
5U Rack Mount units: SU027RM
3U Rack Mount units: SU027RM3U
Because its design is so flexible, Redundant Switch has many
uses. View or download the Redundant Switch Applications Guide
from the Products section of APC’s Web page.
Redundant Switch for Smart-UPS
Specifications SU041 SU042-1 SU042-2 SU045-1
Acceptable input voltage 120 VAC: 0 - 165 VAC 208 VAC: 0 - 275 VAC
Output voltage 120 VAC: 108 - 132 VAC 208 VAC: 187 - 229 VAC
(by default when used with Smart-UPS)
Frequency limits (on-line operation) 47 - 63 HZ
Transfer time at normal sensitivity 6 milliseconds (typical)
Maximum load 1400 VA; 12 A 3000 VA; 14 A 3000 VA; 24 A
Operating temperature 0 to +50 ºC (+32 to +122 ºF)
Storage temperature -15 to +50 ºC (+5 to +122 ºF)
Operating and storage relative humidity 0 to 95%, non-condensing
Operating elevation 0 to +3,000 m (0 to +10,000 ft)
Storage elevation 0 to +15,000 m (0 to +50,000 ft)
Electromagnetic immunity IEC 801-2, 801-3, 801-4
Audible noise in dBA @ 1 m (3 ft) <45
Size (H x W x D) 1.75 x 17.0 x 9 in.
Weight - net (shipping) 10 (15) lb.
Outlet configuration (2) 5-15R (2) 5-15R (1) L5-30 R (1) L6-20 R
Input Configuration (2) 5-15P (2) L5-30P (2) L5-30P (2)L6-20P
Safety approvals Listed to UL 1778, certified to CSA 107.1
EMC verification 120 VAC: FCC Class A certified
19
For more information about all APC products, go to www.apcc.com
Redundant Switch Configuration Table (for best application)
Redundant Switch Model Voltage Rating Max VA Rating Recommended Smart-UPS
1
SU041 120V 1400VA (2) SU700, (2) SU1000, (2) SU1400
SU042-1
2
120V 3000VA (2) SU2200, (2) SU3000
SU042-2
3
120V 3000VA (2) SU2200, (2) SU3000
SU045-1 208V 3000VA T models only (2) SU2200,
(2) SU3000