NetBotz Rack Monitor 450/550 Installation and Quick Configuration Manual20
Add pods to your appliance
The NetBotz Rack Monitor 550 supports the following pods:
A combined total of 4 Camera Pod 160s, Camera Pod 120s, and CCTV Adapter Pod 120s.
A combined total of 12 Sensor Pod 150s, Sensor Pod 155s, Sensor Pod 120s, and
4-20 mA Input Pod 120s.
The NetBotz Rack Monitor 450 supports the following pods:
A combined total of 2 Camera Pod 160s, Camera Pod 120s, and CCTV Adapter Pod 120s.
A combined total of 2 Sensor Pod 150s, Sensor Pod 155s, Sensor Pod 120s, and
4-20 mA Input Pod 120s.
Camera Pods, Sensor Pod 120s, and 4-20 mA Input Pod 120s can be connected directly to any of the
appliance USB ports, or you can connect USB hubs to your appliance and then connect pods to the hub.
Hubs can also be daisy chained, and pods can be connected to the daisy-chained hubs as long as the pod
is no more than the fifth device in the chain.
Note: Due to power requirements, Camera Pod 160s, Sensor Pod 120s,
CCTV Adapter Pod 120s, and 4-20 mA Input Pod 120s must be connected either directly to
one of the USB ports at the appliance or to a USB hub receiving power from an external source.
RS232-based sensors or devices can be connected to unpowered USB hubs.
As pods are connected to your appliance, they automatically appear in the Navigation pane in both the
Basic and Advanced View interfaces. Newly added pods are labeled by their pod type and their serial
number.
Once a pod is added, you can change its label using either the Basic View or the Advanced View.
Once connected, CCTV Adapter Pod 120s require additional configuration before they can be
used.
For more information, see “Install and configure a CCTV Adapter Pod 120” on
page 21.
If you connect a pod and then disconnect it, its entry in the Navigation pane in the Advanced View
is grayed out. If you reconnect a disconnected pod, its Navigation pane entry becomes active
again.