19NetShelter SX Enclosure: Unpacking, Installation, and Customization
3. To align the vertical mounting flanges properly,
note the symbol (for example, the diamond)
visible through the one of the holes on the top of
the flange, and ensure that the same symbol is
visible through the corresponding hole at the
bottom of the flange. Only one symbol is visible
at a time through any of the holes. In the
factory-standard position, the circles are visible
through two of the holes.
On the 750-mm rack there are circles 476 mm
(18.75 in) behind the front mounting flange
designating the location for networking and
telecommunications equipment.
Note: Vertical mounting flanges adjust in 6-mm (1/4-in) increments.
Note: Vertical mounting flanges placed across from each other must have the same
visible symbol.
4. When the vertical mounting flange is in the proper
location, slide each screw up until the teeth in the
bracket engage fully with the teeth in the side brace,
and tighten the screws.