17InRow RC Operation and Maintenance
Run hours
The cooling unit records the number of hours each of its components has operated. When a component is
replaced, use the Reset option to reset the run hours for the displayed component to zero.
Path: Main > View Run Hours > Air Filter
• Air Filter
• Reset Run Hours
Path: Main > View Run Hours > Fans > Fan n
• Fan n
• Reset Run Hours
Path: Main > View Run Hours > Fan Power Supply
• Fan PS LT–Fan Power Supply Left
• Fan PS RT–Fan Power Supply Right
• Reset PS LT Hours
• Reset PS RT Hours
Path: Main > View Run Hours > Condensate Pump
• Condensate Pump
• Reset Run Hours
Thresholds
Set alarms to alert you to high temperature violations.
Path: Main > Set Unit Thresholds
When the air temperature exceeds the temperature defined by the High Temperature Threshold, an
alarm will occur. Set High Temperature Thresholds for the following:
• Rack Inlet: The air entering the rack at the temperature sensor.
• Inlet Fluid: The chilled water entering the cooling unit.
• Supply Air: The air leaving the cooling unit.
• Return Air: The air entering the cooling unit.
Service intervals
Set alarms to alert you when components require service.
Path: Main > Service Intervals
The air filter should be serviced quarterly. The service interval depends on environmental cleanliness.
• Air Filter Interval: Set the number of weeks to service the air filter.
• Alarm: If enabled, an alarm activates when the Air Filter Interval has elapsed (default is 12
weeks). The Air Filter Interval must be manually reset to disable the alarm.