17InRow RC Operation and Maintenance
Run hours
The cooling unit records the number of hours each of its components has operated. When a component is
replaced, use the Reset option to reset the run hours for the displayed component to zero.
Path: Main > View Run Hours > Air Filter
Air Filter
Reset Run Hours
Path: Main > View Run Hours > Fans > Fan n
• Fan n
Reset Run Hours
Path: Main > View Run Hours > Fan Power Supply
Fan PS LT–Fan Power Supply Left
Fan PS RT–Fan Power Supply Right
Reset PS LT Hours
Reset PS RT Hours
Path: Main > View Run Hours > Condensate Pump
• Condensate Pump
Reset Run Hours
Thresholds
Set alarms to alert you to high temperature violations.
Path: Main > Set Unit Thresholds
When the air temperature exceeds the temperature defined by the High Temperature Threshold, an
alarm will occur. Set High Temperature Thresholds for the following:
Rack Inlet: The air entering the rack at the temperature sensor.
Inlet Fluid: The chilled water entering the cooling unit.
Supply Air: The air leaving the cooling unit.
Return Air: The air entering the cooling unit.
Service intervals
Set alarms to alert you when components require service.
Path: Main > Service Intervals
The air filter should be serviced quarterly. The service interval depends on environmental cleanliness.
Air Filter Interval: Set the number of weeks to service the air filter.
Alarm: If enabled, an alarm activates when the Air Filter Interval has elapsed (default is 12
weeks). The Air Filter Interval must be manually reset to disable the alarm.