When the unit is set for a two minute warning interval the configuration LED is brightly lit. When
the unit is set for a five minute warning interval the configuration LED is dimly lit. When the unit is
set for a seven minute warning interval the configuration LED is off.
5.11 Shutdown Mode
In shutdown mode the unit stops supplying power to the load, waiting for the return of utility
power. If there is no utility power present, external devices (e. g., servers) connected to the com-
puter interface or the accessory slot can command the unit to shut down. This is normally done to
preserve battery capacity after the graceful shutdown of protected servers. The unit will scroll the
front panel indicators sequentially in shutdown mode.
6. Alarms
6.1 On Battery
In on-battery operation, the on-battery LED comes on and the unit sounds an audible alarm consisting
of four beeps every 30 seconds. The alarm stops when the unit returns to on-line operation.
Press the on/test button during on-battery alarms to stop the beeping. This works for the current
alarm only — the next on-battery alarm will have the audible indication. Shutting off the audible
alarm in this way does not affect alarm reporting through the computer interface or accessory
slot.
6.2 Overload
When the unit is overloaded (when the connected loads exceed maximum listed in section 12) the
overload LED comes on and the unit emits a sustained tone. The alarm remains on until the over-
load is removed. Disconnect nonessential load equipment from the unit to eliminate the overload.
6.3 Replace Battery
The unit emits short beeps for one minute and the replace battery LED comes on if the battery fails
the self-test. The unit repeats the alarm every five hours. Perform the self-test procedure in section
5.3 to confirm the replace battery condition. The alarm stops when the battery passes the self-test.
6.4 Low Battery
When the units battery is low the unit beeps continuously until the unit returns to on-line operation
or shuts down from battery exhaustion. The low battery warning interval is a configuration item.
See section 5.10.