990-2282 Smart-UPS® VT 10-40kVA, 400V, Operation Manual 23
Restart procedure
Power application
Set the mains breaker to the ON position.
Set the Battery Breaker Box to the ON position following the specifications provided by the
manufacturer.
Note
Start-up is included with the UPS, and the procedure described here is only applicable if
the UPS requires a subsequent start-up.
WARNING!
Only trained personnel familiar with the construction and operation of the equipment
may carry out the Start-Up procedure.
ON
OFF
10/100Base-T
Probe
AP9619 Network Management Card EM
!
Reset
Output
Pwr
Zone
10/100
ON
OFF
Mains
breaker
Battery
Breaker
Box
Battery Bank