DO RUNTIME CAL: screen (Figure 27) — lets you manually initiate a Runtime
Calculation test to calibrate the internal measurements, which should result in
more accurate runtime estimates. This needs to be done once every 6 months, or
when the connected load changes significantly in size. Once initiated, the unit will
operate on battery power until a low battery condition is reached.
Figure 27. DO RUNTIME CAL Screen
DISPLY-BEEP TEST: screen (Figure28) — lets you force the unit to perform
Display and Beep Tests. Simply advance to the DISPLY-BEEP TEST screen and
press either Up/Down Arrow push buttons. This will cause all indicators and display
fields to light (Figure 29), as well as cause an audible beep to sound.
Figure 28. DISPLY-BEEP TEST: Screen