1 990-1013, Revision 1, 7/99
Installation Note for Smart-UPS DP Accessories English
Optional accessories for the Smart-UPS DP include an extended run battery cabinet (SUDPBP1/SUDPBP2) and a service
bypass panel (SUDP001/SUDP002). During the installation of either of these options, you must attach a ferrite bead on
the signal cable to ensure regulatory compliance.
Note:
When installing either the extended run battery cabinet or the service bypass panel, you must complete the following
steps to ensure that the Smart-UPS DP passes all regulatory tests. Failure to complete these installation steps may void
regulatory compliance.
How to Install a Ferrite Bead
1. Follow the installation instructions for the accessory until the wiring is complete. (Refer to the Smart-UPS DP User’s
Manual for instructions.) Leave the back cover of the Smart-UPS DP off.
2. Open the ferrite bead by inserting a coin or finger nail under the lip Πon the side of the ferrite bead and gently lift it
over the ridge . The unit will open in two halves.
3. Squeeze together, twist, or tape the wires connected to the input signal connector (for the particular option) to reduce
the overall diameter.
4. With the ferrite bead open, position the wires in the groove on one side of the ferrite bead.
6)5)
4)
3)
2)
1)
2. REPLACEMENT
1. REPLACEMENT
INSTALLED
YEARMONTH
REPLACEMENT OF BATTERIES
KG.WEIGHT:
S. NO.:
TYPE:
P.NO.:
L
OUTPUT
NNL
INPUT
EXTERNAL BATTERY
BEFORE CONNECTING TO
SEE INSTALLATION INSTRUCTIONS
DANGER
ComPort
Ext. Battery
384V DC
HIGH VOLTAGE
BATT. TEMP. SENSOR
FOR EXTERNAL
TEMP. SENSOR
INTERNAL BATT.
TEMP. SENSOR
FOR BATTERY
TR. TH. SWITCH
FOR EXTERNAL
1 2 3 4
COM. FAULT
1 2 3 4
MBS CONTROL
BLACKRED
BATT. TEMP. SENSOR
FOR EXTERNAL
TEMP. SENSOR
INTERNAL BATT.
TEMP. SENSOR
FOR BATTERY
TR. TH. SWITCH
FOR EXTERNAL
1 2 3 4
COM. FAULT
1 2 3 4
MBS CONTROL
BLACK
RED
Ž Signal connector for the service bypass panel option
Signal connector for the extended run battery cabinet option (shown with ferrite installed)
5. Close the other half of the ferrite bead around the wires until the lip seals (you should hear a “snap” when it closes).
Œ
Ž
Page view 0
1 2

Summary of Contents

Page 1 - MBS CONTROL

1 990-1013, Revision 1, 7/99Installation Note for Smart-UPS DP Accessories EnglishOptional accessories for the Smart-UPS DP include an extended run ba

Page 2

990-1013, Revision 1, 7/99 26. If the Smart-UPS DP has both options, repeat steps 2 through 5 to install the ferrite bead for the second option. The