A-2
Models J15, J15BLK J10, J10BLK
INPUT
Voltage Range for
Operation on Utility
90V – 144V Same
Nominal Voltage 120 Vac Same
Allowable Frequency
for Operation on Utility
47 – 63 Hz Same
Rated Input Current 12 Amps 9 Amps
Circuit Breaker Rating 15 Amps 15 Amps
OUTPUT
# of Outlets 12 (all outlets are
surge protected,
conditioned, regu-
lated and battery
backed up)
Same
Outlet Type NEMA 5-15R Same
Rated VA Capacity 1440 VA 1000 VA
Rated Watt Capacity
(continuous)
865 Watts 600 Watts
Rated Output Current 12 Amps 9 Amps
BATTERY BACKUP
Transfer Time to
Battery During
Blackout
7ms typical,
10ms maximum
Same
Battery Type/Quantity 2 12V/9A hr
Sealed Lead-Acid,
Maintenance Free
2 12V/7A hr
Sealed Lead-Acid,
Maintenance Free
Typical Recharge Time
to 90% Capacity
<16 hrs Same
Battery Service User-replaceable,
Hot-swappable
Same
Comments to this Manuals