7Smart-UPS X-Series Operation
Controllable Outlet Groups
Overview
The rear panel of the UPS has multiple outlets, some are grouped into Controllable Outlet Groups, all
others are the UPS outlets. All of these groups can be configured to turn off, turn on, shut down, and
reboot connected equipment, independently of each other.
The Controllable Outlet Groups and the UPS outlets can be configured to react to power events in
specific ways:
Turn off: Disconnect from power immediately and restart only with a manual command
Turn on: Connect to power immediately
Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when
utility power becomes available
Reboot: Shut down and restart
In addition, the Controllable Outlet Groups and the UPS outlets can also:
Turn on or off in a specified sequence
Shut down when various conditions occur
Note: If the Controllable Outlet Groups are not configured, all of the outlets on the unit will
still provide battery back-up power.
Nominal Output
Voltage
230 V: 230 VAC 230 V: 220, 230, 240
VA C
Set the nominal output voltage of the UPS on
battery. This is available on 230V models
only.
Transfer
Sensitivity
High High, Low, Medium Specify how sensitive the UPS will be
towards voltage changes.
Low Battery
Warning
90 sec 0-300 sec The UPS will emit an audible alarm when the
remaining runtime has reached this level.
Date of Last
Battery
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On On/Off The UPS will mute all audible alarms if this is
set to Off or when the display buttons are
pressed.
Battery Self-
Test Interval
Setting
On start-up and
every 14 days since
the last test
• Never
• Start-up only
• Frequency of test
The interval at which the UPS will execute a
self-test.
Reset to Factory
Default
No Yes/No Restore the UPS factory default settings.