User Configurable Items
User Configurable Items
UPS settings
Settings are adjusted through PowerChute software or optional Network Management Card.
Function
Factory
Default
User Selectable
Choices
Description
Automatic
Self-Test
Every 14 days
(336 hours)
Every 7 days
(168 hours)
On start up only
No self-test
Set the interval at which the UPS will execute a
self-test.
UPS ID UPS_IDEN Up to eight characters
(alphanumeric)
Uniquely identify the UPS (i.e. server name or
location) for network management purposes.
Date of Last
Battery
Replacement
Manufacture
Date
mm/dd/yy Reset this date when you replace the battery
module.
Minimum Capacity
Before Return from
Shutdown
0 percent 0%
15%
30%
45%
60%
75%
90%
Specify the percentage to which batteries will
be charged following a low battery shutdown
before powering connected equipment.
Voltage Sensitivity High sensitivity High sensitivity
Medium sensitivity
Low sensitivity
The UPS detects and reacts to line voltage
distortions by transferring to battery operation
to protect the connected equipment.
In situations of poor power quality, the UPS
may frequently transfer to battery operation. If
the connected equipment can operate normally
under such conditions, reduce the sensitivity
setting to conserve battery capacity and service
life.
Alarm Delay
Control
Enable Enable
Mute
Disable
Mute ongoing alarms or disable all alarms
permanently.
Shutdown Delay 90 seconds 0 s
90 s
180 s
270 s
360 s
450 s
540 s
630 s
Set the interval between the time when the UPS
receives a shutdown command and actual
shutdown.