3. The enclosures can be joined so that their centers are 30 in or 750 mm apart. Align the enclosures
to use the appropriate holes on the front and rear of the enclosures for the spacing you need and
secure the enclosures using one M5 x 12 flat-head screw per bracket.
4. If the enclosures are joined together on 30-in centers, there is a gap between them. APC offers
optional baying trim (AR7600) to cover the gap between the enclosures. The trim snaps into
place without tools and can be installed after the units are joined together and have equipment
installed in them.
Note: 750-mm enclosures join together without a gap when joined using the inner-most
set of holes on the joining brackets.
5. Reconnect the grounding wires, and reinstall the doors, if needed.
See “Installing the doors” on page 12.
To connect a NetShelter SX enclosure to a NetShelter VX or NetShelter VS enclosure, APC offers a
separate joining kit (AR7601 for enclosures with 600-mm centers or AR7602 for enclosures with 24-in
centers). When using the AR7601, the NetShelter SX enclosure will be inset by 33.2 mm (1.3 in) from
the VX or VS enclosure.