InRow RD 100-Series and InRow RD 200-Series User’s Guide17
The value InRow RD should always display in the unit-type field. You can group InRow RD 100-series
and InRow RD 200-series units, but do not attempt to connect other cooling-unit models to the group.
Doing so may cause communication problems and prevent the group from operating correctly.
To configure the name and location of a unit, see “Identification” on page 18.
Viewing and Configuring Unit Settings
Status > Overview page
The Overview page, which displays by default the first time you select the Unit tab, provides basic unit
status information.
• Operating Mode—The current operating mode of the unit:
– On—The unit is providing cooling.
– Standby—The user turned off the cooling functions of the unit, or the input contact is in an
abnormal state.
– Idle—The unit is not providing cooling because it has active alarms.
– Refrig—The unit is in Refrigerant Fill mode.
• Compressor State—The present operating status (on or off) of the compressor for this unit.
• Cool Output—The amount of cooling provided by the unit.
• Cool Demand—The amount of cooling that is currently required.
• Rack Inlet Temperature—The temperature of air entering the enclosure.
• Supply Air Temperature—The temperature of air leaving the unit.
• Return Air Temperature—The temperature of air entering the unit.
• Suction Temperature—The temperature of the low pressure (suction) refrigerant line.
• Air Flow—The amount of air that must flow through the evaporator to maintain the setpoint
temperature.
• Fan Speed—The speed of the fans that regulate air flow through the evaporator.
• Fluid Valve Position (ACRD100)—The position of the valve that regulates fluid flow through
the unit (0% indicates that the valve is fully closed and 100% indicates that it is fully opened).
• Hot Gas Bypass Valve Position (ACRD200)—The position of the valve that regulates hot gas
bypass (0% indicates that the valve is fully closed and 100% indicates that it is fully opened).