APC IN ROW RD ACRD101 User's Guide Page 64

  • Download
  • Add to my manuals
  • Print
  • Page
    / 76
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 63
InRow RD 100-Series and InRow RD 200-Series User’s Guide57
The Upload Event and Error Messages
The event and its error messages
The following event occurs when the receiving cooling unit completes using the .ini file to update its
settings.
Configuration file upload complete, with number valid values
If a keyword, section name, or value is invalid, the upload by the receiving cooling unit succeeds, and
additional event text states the error.
Messages in config.ini
A device associated with the cooling unit from which you download the config.ini file must be
discovered successfully in order for its configuration to be included. If the device is not present or, for
another reason, is not discovered, the config.ini file contains a message under the appropriate section
name, instead of keywords and values.
If you did not intend to export the configuration of the device as part of the .ini file import, ignore these
messages.
Errors generated by overridden values
The Override keyword and its value will generate error messages in the event log when it blocks the
exporting of values.
See “Contents of the .ini file” on page 55 for information about which values are overridden.
Because the overridden values are device-specific and not appropriate to export to other cooling units,
ignore these error messages. To prevent these error messages, you can delete the lines that contain the
Override keyword and the lines that contain the values that they override. Do not delete or change the
line containing the section heading.
Event text Description
Configuration file warning: Invalid keyword
on line number.
Configuration file warning: Invalid value on
line number.
A line with an invalid keyword or value is ignored.
Configuration file warning: Invalid section on
line number.
If a section name is invalid, all keyword/value pairs in that
section are ignored.
Configuration file warning: Keyword found
outside of a section on line number.
A keyword entered at the beginning of the file (i.e., before
any section headings) is ignored.
Configuration file warning: Configuration file
exceeds maximum size.
If the file is too large, an incomplete upload occurs. Reduce
the size of the file, or divide it into two files, and try
uploading again.
Page view 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 75 76

Comments to this Manuals

No comments