Graceful shutdown sequence for On-battery events
Low Battery Warning Control
Never On Runtime Remaining
Is there a cable connected to the Basic Port?
No Yes
Device Confirm
Ye s N o
Power On Delay
Remain Off Delay
Outlet is on
UPS indicates AC power failure
Programmed Delay
UPS battery is
exhausted
UPS indicates AC
power restored or
Cancel command is
issued
Outlet is
turned off
Server confirms shutdown
Power Off Delay expires
Outlet is turned off
UPS is operating on AC power
UPS exceeds Battery Capacity Threshold
or
Battery Capacity Threshold Override command is issued
MasterSwitch Plus Asserts AC Fail Signal
MasterSwitch Plus
Asserts Low
Battery Signal
Outlet Property
This diagram sequences the events
that an outlet set to Graceful Shutdown
will follow when your UPS goes on
battery. The sequence is an
unattended operation that requires you
to choose values for the following
properties:
Low Battery Warning Control
UPS Low Battery Multiplier
Device Confirm
Power Off Delay
Battery Capacity Threshold
Power On Delay
Shutdown
Restart
Outlet
remains off
You issue a
Cancel
command
Power On
Delay
expires
Outlet is
turned on
Programmed
Delay Expires
UPS runtime remaining falls below UPS Low
BatteryWarning Threshold x Low Battery Multiplier