Configure Outlets
Web interface. Click the outlet number link (for example 1:3) and make
changes to Outlet Name, Outlet Mode, and Outlet Links. Click Apply to
accept the changes.
Control console. To configure outlets individually, select the MasterSwitch
Plus unit you want to control from the Device Manager menu, and select
the outlet you want to configure. Select Outlet Configuration and choose a
configuration setting from the list. Select Accept Changes to apply the new
settings.
Setting Description
Outlet Name Identifies each outlet.
Outlet Control
Mode
Establishes mode for associated outlet. All on-demand operations are
available when the Outlet Control mode is set to Graceful Shutdown.
When set to Annunciator, only Immediate On and Immediate Off
operations are available.
Outlet Link
(Web only)
The Outlet’s HTTP link in URL form or a Telnet address.
Will Device
Confirm
Indicates whether the device connected to the outlet can assert a
shutdown signal.
Low Battery
Warning
Control
Selects the method MasterSwitch Plus uses for determining when to
assert the outlet’s Low Battery signal after the UPS has switched to
battery operation.
UPS Low
Battery
Multiplier
A low battery signal is generated when the UPS's remaining battery
runtime falls below this value multiplied by the UPS Low Battery
Warning.
Restart Delay The delay between removing power from an outlet due to a Graceful
Shutdown and reapplying power to that outlet.
Power Off
Delay
The time from the triggering event (such as a server confirming a
shutdown) until power is removed from the outlet.